Technical parameters of high temperature water-cooled box unit
MODEL | KG-3W | KG-5W | KG-6W | KG-8W | KG-10W | KG-12W | KG-15W | |
Refrigerating capacity | KW | 8.8 | 14.6 | 17.8 | 23.8 | 29 | 34.9 | 43.9 |
Kcal/h | 7568 | 12556 | 15308 | 20468 | 24940 | 30014 | 37754 | |
Rated power of the whole machine (KW) | 2.8 | 4.3 | 5.05 | 7 | 8.5 | 10 | 13.45 | |
Input power supply | 380V/3PH/50Hz | |||||||
Whole machine current (A) | 6 | 9 | 11 | 14 | 17 | 20 | 27 | |
Compressor | Type | Fully enclosed vortex type | ||||||
Rated power (KW) | 2.25 | 3.75 | 4.5 | 3*2 | 3.75*2 | 4.5*2 | 3.75+7.5 | |
Condenser | Type | High-efficiency shell tube type | ||||||
Cooling water flow rate (m³ / h) | 2 | 3.3 | 4 | 5.3 | 6.5 | 7.8 | 9.8 | |
Evaporator | Type | The coil type | ||||||
Flow rate of refrigerant (m³ / h) | 1.5 | 2.5 | 3.1 | 4.1 | 5 | 6 | 7.6 | |
Tank capacity (L) | 50 | 50 | 50 | 150 | 150 | 150 | 150 | |
Inlet and outlet of the water pipe diameter | DN25 | DN25 | DN25 | DN40 | DN40 | DN40 | DN50 | |
Water pump | Rated power (KW) | 0.55 | 0.55 | 0.55 | 1 | 1 | 1 | 2.2 |
Lift (m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |
Refrigerant | Name | R22 / R134a / R407c | ||||||
Filling capacity (Kg) | 1.8 | 3 | 3.6 | 4.8 | 6 | 7.2 | 9 | |
Control method | Expansion valve / capillary tube | |||||||
Safety precautions | Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, anti-freezing protection, water flow switch protection | |||||||
Dimensions | Length (mm) | 882 | 882 | 882 | 1404 | 1404 | 1404 | 1404 |
Width (mm) | 524 | 524 | 524 | 694 | 694 | 694 | 694 | |
Height (mm) | 1250 | 1250 | 1250 | 1514 | 1514 | 1514 | 1514 | |
Weight | Kg | 130 | 150 | 150 | 300 | 430 | 735 | 735 |
Technical parameters of high temperature water-cooled box unit
MODEL | KG-20W | KG-25W | KG-30W | KG-40W | KG-50W | KG-60W | |
Refrigerating capacity | KW | 61 | 72 | 91.5 | 122 | 144 | 174 |
Kcal/h | 52460 | 61920 | 78690 | 104920 | 123840 | 149640 | |
Rated power of the whole machine (KW) | 17.2 | 20.2 | 25.5 | 34 | 40 | 49 | |
Input power supply | 380V/3PH/50Hz | ||||||
Whole machine current (A) | 35 | 41 | 51 | 68 | 80 | 98 | |
Compressor | Type | Fully enclosed vortex type | |||||
Rated power (KW) | 7.5*2 | 9*2 | 7.5*3 | 7.5*4 | 9*4 | 11.25*4 | |
Condenser | Type | High-efficiency shell tube type | |||||
Cooling water flow rate (m³ / h) | 13.7 | 16.1 | 20.4 | 27.3 | 32.2 | 39 | |
Evaporator | Type | High-efficiency shell tube type | |||||
Flow rate of refrigerant (m³ / h) | 10.5 | 12.4 | 15.7 | 21 | 24.8 | 30 | |
Tank capacity (L) | 200 | 200 | 300 | 400 | 500 | 700 | |
Inlet and outlet of the water pipe diameter | DN50 | DN65 | DN65 | DN80 | DN80 | DN80 | |
Water pump | Rated power (KW) | 2.2 | 2.2 | 3 | 4 | 4 | 4 |
Lift (m) | 20 | 20 | 20 | 20 | 20 | 20 | |
Refrigerant | Name | R22 / R134a / R407c | |||||
Filling capacity (Kg) | 12 | 15 | 18 | 24 | 30 | 36 | |
Control method | Expansion valve / capillary tube | ||||||
Safety precautions | Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, anti-freezing protection, water flow switch protection | ||||||
Dimensions | Length (mm) | 1704 | 1704 | 2102 | 2305 | 2305 | 3004 |
Width (mm) | 774 | 774 | 814 | 954 | 954 | 954 | |
Height (mm) | 1765 | 1765 | 1470 | 1875 | 1875 | 1874 | |
Weight | Kg | 820 | 900 | 1150 | 1200 | 1250 | 1300 |
Nominal cooling capacity: the inlet and outlet temperature of cooling water is 32℃ / 37℃, and the inlet and outlet temperature of carrying refrigerant is 12℃ / 7℃
The Company reserves the power to change the technology without notice of any change