Technical parameters of the high-temperature air-cooled box-type unit
MODEL | KG-1AN | KG-2AN | KG-3A | KG-5A | KG-6A | KG-8A | KG-10A | KG-12A | |
Refrigeration capacity | KW | 2.67 | 5.35 | 8 | 13 | 16 | 21.4 | 26.7 | 32 |
Kc aI/h | 2296 | 4601 | 6880 | 11180 | 13760 | 18404 | 22962 | 27520 | |
Rated power of the whole machine (KW) | 1.22 | 2.035 | 2.98 | 4.7 | 5.45 | 7.85 | 9.35 | 10.85 | |
Input power supply | 220V /3P H /50Hz | 380V/3PH/50Hz | |||||||
Whole machine current (A) | 3 | 5 | 6 | 10 | 11 | 16 | 19 | 22 | |
Compressor | Type | Fully enclosed vortex type | |||||||
Rated power (KW) | 0.75 | 1.5 | 2.25 | 3.75 | 4.5 | 3*2 | 3.75*2 | 4.5*2 | |
Condenser | Type | High-efficiency copper tube sleeve aluminum wing type + low noise external rotor fan | |||||||
Cooling air volume | 1000 | 2000 | 3000 | 5000 | 6000 | 8000 | 10000 | 12000 | |
Fan power (KW) | 0.1 | 0.165 | 0.18 | 0.4 | 0.4 | 0.85 | 0.85 | 0.85 | |
Evaporator | Type | Coil / plate / shell tube type | |||||||
Flow rate of refrigerant | 0.46 | 0.92 | 1.38 | 2.24 | 2.8 | 3.68 | 4.6 | 5.5 | |
Tank capacity (L) | 20 | 20 | 50 | 50 | 50 | 150 | 150 | 150 | |
Inlet and outlet of the water pipe diameter | DN25 | DN25 | DN25 | DN25 | DN25 | DN40 | DN40 | DN40 | |
Water pump | Rated power (KW) | 0.37 | 0.37 | 0.55 | 0.55 | 0.55 | 1 | 1 | 1 |
Lift (m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |
Refrigerant | Name | R22 / R134A / R407C | |||||||
Filling capacity (Kg) | 0.6 | 1.2 | 1.8 | 3 | 3.6 | 4.8 | 6 | 7.2 | |
Control method | Capillary / expansion valve | ||||||||
Safety precautions | Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, frost protection | ||||||||
Dimensions | Length (mm) | 650 | 800 | 864 | 963 | 963 | 1243 | 1243 | 1243 |
Width (mm) | 460 | 580 | 634 | 633 | 633 | 863 | 863 | 863 | |
Height (mm) | 750 | 750 | 1443 | 1475 | 1475 | 1920 | 1920 | 1920 | |
Weight | Kg | 140 | 140 | 140 | 210 | 210 | 300 | 350 | 350 |
Technical parameters of the high-temperature air-cooled box-type unit
MODEL | KG-15A | KG-20A | KG-25A | KG-30A | KG-40A | KG-50A | KG-60A | |
Refrigeration capacity | KW | 40.1 | 55.4 | 64 | 83 | 110.8 | 128 | 154 |
Kcal /h | 34486 | 47644 | 55040 | 71380 | 95288 | 110080 | 132440 | |
Rated power of the whole machine (KW) | 14.65 | 18.9 | 21.9 | 28.05 | 37.4 | 43.4 | 52.4 | |
Input power supply | 380V /3P H /50Hz | |||||||
Whole machine current (A) | 30 | 38 | 44 | 57 | 75 | 87 | 105 | |
Compressor | Type | Fully enclosed vortex type | ||||||
Rated power (KW) | 7.5+3.75 | 7.5*2 | 9*2 | 7.5*3 | 7.5*4 | 9*4 | 11.25*4 | |
Condenser | Type | High efficiency copper tube sleeve aluminum wing type + low noise external rotor fan | ||||||
Cooling air volume (m³ / h) | 15000 | 20000 | 25000 | 30000 | 40000 | 50000 | 60000 | |
Fan power (KW) | 0.4*3 | 0.85*2 | 0.85*2 | 0.85*3 | 0.85*4 | 0.85*4 | 085*4 | |
Evaporator | Type | Cooil / plate / shell tube type | ||||||
Flow rate of refrigerant | 6.9 | 9.5 | 11 | 14.3 | 19.1 | 22 | 26.5 | |
Tank capacity (L) | 200 | 300 | 300 | 300 | 400 | 400 | 400 | |
Inlet and outlet of the water pipe diameter | DN50 | DN50 | DN65 | DN65 | DN80 | DN80 | DN80 | |
Water pump | Rated power (KW) | 2.2 | 2.2 | 2.2 | 3 | 4 | 4 | 4 |
Lift (m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |
Refrigerant | Name | R22 / R134A / R407C | ||||||
Filling capacity (Kg) | 9 | 12 | 15 | 18 | 24 | 30 | 36 | |
Control method | Capillary / expansion valve | |||||||
Safety precautions | Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, frost protection | |||||||
Dimensions | Length (mm) | 2001 | 2604 | 2604 | 2523 | 2100 | 2100 | 2300 |
Width (mm) | 854 | 904 | 904 | 954 | 1925 | 1925 | 2110 | |
Height (mm) | 1608 | 1915 | 1915 | 2024 | 1990 | 1990 | 2254 | |
Weight | Kg | 650 | 800 | 980 | 1050 | 1250 | 1450 | 1650 |
Technical parameters of high-temperature air-cooled box unit (new 410 refrigerant)
MODEL | KG-3AQ | KG-5AQ | KG-8AQ | KG-10AQ | KG-12AQ | KG-15AQ | KG-20AQ | KG-25AQ | |
Refrigeration capacity | KW | 8 | 13 | 21.4 | 26.7 | 32 | 40.1 | 55.4 | 65 |
KcaI/h | 6880 | 11180 | 18404 | 22962 | 27520 | 34486 | 47644 | 55900 | |
Rated power of the whole machine (KW) | 3.3 | 4.8 | 7.8 | 9.3 | 10.8 | 14.45 | 18.8 | 22.55 | |
Input power supply | 380V/3PH/50Hz | ||||||||
Whole machine current (A) | 7 | 10 | 16 | 19 | 22 | 29 | 38 | 46 | |
Compressor | Type | Fully enclosed vortex type | |||||||
Rated power (KW) | 2.25 | 3.75 | 6 | 7.5 | 9 | 11.25 | 15 | 18.75 | |
Condenser | Type | High-efficiency heat exchanger + low noise external rotor fan | |||||||
Cooling air volume (m³ / h) | 3000 | 5000 | 8000 | 10000 | 12000 | 15000 | 20000 | 25000 | |
Fan power (KW) | 0.25*2 | 0.25*2 | 0.4*2 | 0.4*2 | 0.4*2 | 0.5*2 | 0.8*2 | 0.8*2 | |
Evaporator | Type | Plate-type | |||||||
Flow rate of refrigerant | 1.4 | 2.2 | 6 | 4.6 | 5.5 | 6.9 | 9.5 | 11.2 | |
Inlet and outlet pipe diameter of carrying cooling agent | DN25 | DN25 | DN40 | DN40 | DN40 | DN40 | DN40 | DN40 | |
Refrigerant | Name | R410 | |||||||
Filling capacity (Kg) | 3 | 3 | 7.2 | 7.2 | 7.2 | 9 | 12 | 15 | |
Control method | Capillary / expansion valve | ||||||||
Water pump | Rated power (KW) | 0.55 | 0.55 | 1 | 1 | 1 | 2.2 | 2.2 | 2.2 |
Lift (m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |
Water box | Capacity (L) | 70 | 70 | 150 | 150 | 150 | 150 | 300 | 300 |
Safety precautions | Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, frost protection | ||||||||
Dimensions | Length (mm) | 1150 | 1150 | 1600 | 1600 | 1600 | 1780 | 2100 | 2100 |
Width (mm) | 680 | 680 | 760 | 760 | 760 | 800 | 904 | 904 | |
Height (mm) | 1309 | 1309 | 1684 | 1684 | 1684 | 1615 | 1980 | 1980 | |
Weight | Kg | 190 | 190 | 370 | 370 | 370 | 800 | 980 | 980 |
●The distribution power of KG-20AQ unit needs to be amplified by a factor of 1.2 on the basis of rated power
● The distribution power of KG-10 AQ unit shall be amplified by a coefficient of 1.2 based on the rated power
● The distribution power of KG-3 AQ unit shall be amplified by a coefficient of 1.46 on the rated power
Nominal cooling capacity: the inlet and outlet temperature of cooling water is 32℃ / 37℃, and the inlet and outlet temperature of carrying refrigerant is 12℃ / 7℃
The Company reserves the power to change the technology without notice of any change