Technical parameters of the medium temperature air-cooled box type unit

MODEL

KZ-3AD

KZ-5AD

KZ-10AD

KZ-15AD

KZ-20AD

KZ-30AD

KZ-40AD

Refrigeration capacity (KW)

-5℃

4.2

6.95

14.7

21.65

29.4

44.1

58.8

-15℃

3.06

5.4

10.81

16.21

21.62

32.43

43.24

-25℃

2.07

3.64

7.25

10.89

14.5

21.75

29

-35℃

1.32

2.36

4.47

6.83

8.94

13.41

17.88

Total power (KW)

2.8

4.7

9.45

13.55

17.9

27.25

37.4

Input power supply

380V/3PH/50Hz

Whole machine current (A)

6

10

19

28

36

55

75

Compressor

Type

Fully enclosed vortex type / semi-enclosed piston type

Rated power (KW)

2.25*1

3.75*1

7.5*1

7.5+3.75

7.5*2

7.5*3

7.5*4

Condenser

Type

High-efficiency copper tube sleeve aluminum wing type + low noise external rotor fan

Cooling air rate (m³ / h)

3000

5000

10000

15000

20000

30000

40000

Fan power (KW)

0.18

0.4

0.85

0.4*3

0.85*2

0.85*3

0.85*4

Evaporator

Type

Shell type / plate type

Tank capacity (L)

35

35

100

200

300

450

500

Flow rate of refrigerant (m³ / h)

1

1.65

3.5

5.14

7

10.5

14

Inlet and outlet of the water pipe diameter

DN25

DN25

DN32

DN40

DN40

DN50

DN60

Circulating pump

Rated power (KW)

0.37

0.55

1.1

1.1

1.2

2.2

4

Lift (m)

20

20

20

20

20

20

20

Refrigerant

Name

R404A / R22 / R407C

Filling capacity (Kg)

1.8

3

6

9

12

18

24

Control mode 

Expansion valve

Safety precautions

Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, frost protection

Dimensions

Length (mm)

864

964

1244

2001

2604

2523

2100

Width (mm)

634

634

864

854

904

874

1925

Height (mm)

1443

1478

1921

1608

1915

2024

1990

Weight

Kg

130

165

400

750

850

1050

1150

Nominal cooling capacity: ambient temperature 35℃, inlet and outlet temperature of carrier cooling agent 0℃ / -5℃ carrier cooling agent is ethylene glycol water solution

    The  Company reserves the power to change the technology without notice of any change